The PPM-TDD1A liquid-cooled conductivity sensor employs advanced anti-polarization and signal isolation technologies to effectively eliminate external interference, ensuring precise and stable performance even in complex electromagnetic environments; it also integrates a temperature sensor to enable real-time, automatic measurement compensation. Easy to install and compatible with various media—such as propylene glycol, ethylene glycol, and deionized water—it provides reliable safety assurance for liquid cooling systems.
■ Compact size, easy to install
■ Ultra-low conductivity (≥2 μS/cm)
■ Highly responsive and accurate
■ Corrosion-resistant
■ Built-in temperature sensor for real-time temperature compensation
| Parameter | Technical Specifications |
| Measurement Principle | Electrochemical |
| Main Material | 316L |
| Compatible Media | Deionized water, PG25, EG25 |
| Electrode Constant | 2-pole, K=0.1 |
| O-ring Material | EPDM |
| Process Connection | G3/4″ bottom thread |
| Sealing Method | Face seal / Tri-clamp / Custom |
| Cable Connection | Direct cable output; M16 waterproof connector optional |
| Accuracy | ±1% FS |
| Resolution | 1 μS/cm |
| Power Consumption | <0.2 W |
| Operating Temperature | 0 to +60°C |
| Temperature Sensor | Pt1000 / Pt100 / NTC10K / 2.252K (selectable) |
| Measurement Range | 0–2000 μS/cm (customizable up to 10,000 μS/cm) |
| Power Supply | 7–30 V DC |
| Output | 4–20 mA & RS485 |
| Response Time | 1 s |
| Max. Pressure Rating | <1 MPa (10 bar) |
| Compensation Mode | Automatic |
| Ingress Protection | IP68 |
| Storage Conditions | 10–60°C @ 20%–90% RH |
| Cable Length | Default 5 m; other lengths customizable |